Johnson Controls TEC3010 Installation Instructions Manual page 36

Tec3000 series wireless proportional fan coil and individual zone thermostat controllers with dehumidification capability
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

Table 10: Menus and Submenus (Part 4 of 8)
Level 1
Level 2
(LCD Screen Name)
Control Setup
Deadband*
(Cont)
Auto Economizer Tuning
Heat Prop Band*
Heat Integral Time*
Heat Process Range*
Heat Saturation Time*
Heat Time Constant*
Heat Process Dead Time*
Heat Period*
Cool Prop Band*
Cool Integral Time*
Cool Process Range*
Cool Saturation Time*
Cool Time Constant*
Cool Process Dead Time*
Cool Period*
Equipment Size
TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Level 3
(Default Values)
0.7 to 1.5°F
Enable
160°F
729 seconds
40°F
600 seconds
720 seconds
72 seconds
60 seconds
160°F
729 seconds
40°F
600 seconds
720 seconds
72 seconds
60 seconds
Normal
Capability Installation Instructions
36
1
Available Values
1.0°F (-17.22 °C)
*Functionally, this is the PID deadband
when the Temp Control Setup is equal to
the Deadband Override or Manual PID
Tuning. When the Temp Control Setup
equals the On/Off Control, the Deadband
is used for the On/Off range of the stage
equipment. This parameter is hidden
when Temp Control Setup equals
Automatic PID Tuning.
Disable or Enable
5 to 10°F (-15 to -1.11°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
300 to 1,600 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
10 to 100°F (-12.22 to 37.77°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
60 to 900 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
360 to 1,440 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
20 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
30 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
5 to 10°F (-15 to -1.11°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
300 to 1,600 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
10 to 100°F (-12.22 to 37.77°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
60 to 900 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
360 to 1,440 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
20 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
30 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
Normal or Oversized