Table 6: Setpoint Operation
Mode of Setpoint
Operation
Occ Setpoint Select =
Setpoint Offset and
Heat Cool Setpoint Mode =
Common Setpoint
Occ Setpoint Select = Min
and Max Setpoints and
Heat Cool Setpoint Mode =
Common Setpoint
Configuring Occupancy
To adapt to nearly any application, the TEC3000 controller supports a wide variety of occupancy sources, such as:
•
Local stand-alone weekly scheduler
•
External schedule from the BAS
•
Occupancy sensor (internal or remote)
•
Occupancy binary input (configurable)
•
Manual occupancy override
•
Temporary occupancy (by interacting with the screen while unoccupied)
•
Temporary occupancy binary input
Occupancy is determined using a top-down decision matrix as shown in Table 7.
TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Details
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
also a common Setpoint Offset (warmer/cooler adjust) that is only applied to Common
Setpoint. Otherwise, this setting works the same as when Occ Setpoint Select = Setpoint
Offset and Heat Cool Setpoint Mode = Individual Setpoints.
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
a configurable range for Common Setpoint, Min Setpoint, and Max Setpoint.