Electronic Thermal Function - Omron 3G3JX Quick Start Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Hide thumbs Also See for 3G3JX:
Table of Contents

Advertisement

PROGRAMMING JX

3.13 Electronic thermal function

This function electronically protects the motor from overheating.
Causes an overload trip (E05) to protect the motor from overheating by setting according to the motor rated current.
Provides the most appropriate protection characteristics, taking into account the decline of a standard motor cooling capabil-
ity at a low speed.
To set a value over the rated current of the motor, be careful of any temperature rise of the motor.
Parameter
b012
Electronic thermal level
b212*
2nd electronic thermal level
b013
Electronic thermal characteristics selection
b213*
2nd electronic thermal characteristics
selection
Related parameters
* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.
Electronic thermal level (motor protection level)
(Example) 3G3JX-AB007, rated current: 4.0 A, setting range: 0.8 to 4.0 A.
Electronic thermal characteristics
Frequency characteristics are multiplied by the b012/212 set value above. The lower the output frequency is, the lower the cool-
ing capability of the standard motor's self-cooling fan.
Reduced torque characteristics 1 - Multiplied by the time limit characteristics set in b012/212 for each frequency.
Constant torque characteristics - Do not skip this setting when using a constant torque motor. Multiplied by the time limit
characteristics set in b012/212 for each frequency.
Reduced torque characteristics 2 - Multiplied by the limit characteristics set in b012/212 for each frequency.
Reduced torque
characteristics 1
Electronic thermal level
Electronic thermal level
X1.0
X0.8
X0.6
0
5
20
60
JX Quick Start Guide
Parameter name
0.2 x Rated current to 1.0 x Rated current
00: Reduced torque characteristics 1
01: Constant torque characteristics
02: Reduced torque characteristics 2
C021
Time before trip (s)
60
4
0
4.6
6.0
(116%)
(150%)
Constant torque
characteristics
Electronic thermal level
X1.0
X0.667
Inverter output
frequency (Hz)
5
0
Description
Example where electronic
thermal level is b012 = 5.0 A
Motor current (A)
(Ratio to the rated
8.0
(200%)
current of the Inverter)
Electronic thermal level
X1.0
X0.8
Inverter output
frequency (Hz)
60
Reduced torque
characteristics 2
Inverter output
frequency (Hz)
0
20
60
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents