Daikin Sensira Series Service Manual page 89

Split r32
Table of Contents

Advertisement

Problem solved?
Repair procedures
To remove the main PCB
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
a U
b V
c W
d DC+
e DC–
INFORMATION
When measuring on the front of the main PCB, make sure to locally remove the
protective varnish with the test leads of the multi meter.
VDC
Com
U
DC+
V
DC+
W
DC+
DC–
U
DC–
V
DC–
W
Are the test results OK?
Yes
No
After all checking procedures listed above have been performed:
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
e
Ref
VDC
0.501 V
DC+
0.501 V
DC+
0.501 V
DC+
0.501 V
0.501 V
0.501 V
Action
Power module is OK. Return to
"Checking
main PCB and continue with the next
procedure.
Replace the main PCB, see
procedures" [
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
2
Components
|
a
b
c
d
Com
U
V
W
U
DC–
V
DC–
W
DC–
4
procedures" [
 84] of the
"Repair
4
 89].
Ref
O.L
O.L
O.L
O.L
O.L
O.L
Service manual
89