Daikin Sensira Series Service Manual page 48

Split r32
Table of Contents

Advertisement

2
|
Components
To perform an insulation check of the compressor
Service manual
48
Prerequisite: First perform an electrical check of the compressor, see
"2.2.1 Checking
procedures" [
Prerequisite: Stop the unit operation via the user interface.
1 Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2 Remove the cover of the compressor wire terminals.
a Compressor wire terminals cover
3 Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.
U Wire terminal U
V Wire terminal V
W Wire terminal W
4
 44].
a
V
U
W
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02