Troubleshooting
1.6.10 Unit discharges white mist
1.6.11 Swing flap does not operate
Service manual
36
Check
Check installation conditions.
Check installation conditions.
Air filter.
Fan motor.
Symptom
Swing flap does not
operate
Detail
▪
Humid site.
▪
Dirty site.
▪
Oil mist.
Dirty heat exchanger.
Dirty air filter.
Defective fan motor.
Check
Check swing flap motor
Check indoor unit PCB
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Detail
Some functions can force
the swing flap into a fixed
position, although swing
mode is selected on the
remote controller. This is
not a unit error, but a
control function to
prevent draft to the
customer.
Connector connection
Split Sensira R32
ESIE18-12E – 2021.02