Components
To install the expansion valve motor with clip
To install the expansion valve motor with bracket
Service manual
60
1 Install the expansion valve motor on the expansion valve body.
INFORMATION
The expansion valve motor is equipped with a pipe retention clip. Install the pipe
retention clip over the pipe to lock the expansion valve motor.
a Expansion valve motor
b Pipe retention clip
c Pipe
2 Route the expansion valve motor harness towards the appropriate PCB.
3 Connect the expansion valve motor connector to the appropriate PCB.
WARNING
When reconnecting a connector to the PCB, make sure to connect it on the correct
location and do NOT apply force, as this may damage the connector or connector
pins of the PCB.
4 Fix the expansion valve motor harness using new tie straps.
5 Install the insulation cap on the expansion valve motor (if applicable).
Is the problem solved?
Yes
No
1 Install the expansion valve motor on the expansion valve body.
INFORMATION
The expansion valve motor is equipped with a metal bracket. Fit the nipples of the
metal bracket into the notches of the expansion valve body.
CAUTION
Make sure to install the expansion valve motor in the correct position (orientation).
a
b
c
Action
No further actions required.
Return to
procedures" [
valve and continue with the next
procedure.