Daikin Sensira Series Service Manual page 45

Split r32
Table of Contents

Advertisement

To perform an electrical check of the compressor
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
2 Visually check:
▪ For oil drops around the compressor. Locate and fix as needed.
▪ Pipes for signs of damage. Replace pipes as needed.
3 Check that the compressor bolts are correctly fixed. Fix as needed.
4 Check that the compressor wire terminals cover is correctly installed and
fixed. Correct as needed.
5 Check the compressor dampers for any damage.
a
1 Damper
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Yes
No
1 First perform a mechanical check of the compressor, see
4
procedures" [
 44].
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2 Remove the cover of the compressor wire terminals.
a
Action
Perform an electrical check of the
compressor, see
"2.2.1 Checking
4
procedures" [
 44].
Replace the compressor and/or
damaged dampers, see
4
procedures" [
 49].
2
Components
|
"2.2.2 Repair
"2.2.1  Checking
Service manual
45