A5-00 - Outdoor Unit: High Pressure Peak Cut / Freeze Protection Problem - Daikin Sensira Series Service Manual

Split r32
Table of Contents

Advertisement

1
|
Troubleshooting
1.5.2 A5-00 – Outdoor unit: High pressure peak cut / freeze protection problem
Service manual
8
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
During cooling operation,
indoor heat exchanger
temperature is below 0°C
(freeze‑up protection
control).
During heating operation,
indoor heat exchanger
temperature is above
65°C (heating peak‑cut
control).
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check for objects near the indoor unit that may block the airflow. See
"3.3 External
factors" [
Possible cause: Airflow of the indoor unit is blocked.
2 Clean the air filter of the indoor unit(s). See "4 Maintenance" [
Possible cause: Faulty or dirty air filter.
3 Clean the indoor unit heat exchanger. See "4 Maintenance" [
Possible cause: Dirty indoor unit heat exchanger.
4 Perform a check of the indoor unit heat exchanger thermistor. See
"2.13 Thermistors" [
Possible cause: Faulty indoor unit heat exchanger thermistor.
5 Perform a check of the indoor unit main PCB. See
4
PCB" [
 67].
Possible cause: Faulty indoor unit main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Effect
Unit will stop operating.
4
 136].
4
 117].
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Reset
Automatic reset when
temperature is within
range.
4
 138].
4
 138].
"2.6  Indoor unit main
Split Sensira R32
ESIE18-12E – 2021.02