Daikin Sensira Series Service Manual page 86

Split r32
Table of Contents

Advertisement

2
|
Components
To check the fuse of the main PCB
To check the rectifier voltage of the main PCB
Service manual
86
2 Check that all wires are properly connected and that all connectors are fully
plugged‑in.
3 Check that no connectors or wires are damaged.
4 Check that the wiring corresponds with the wiring diagram, see
4
diagram" [
 142].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Yes
No
Prerequisite: First perform all earlier main PCB checks, see
4
procedures" [
 84].
1 Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
c
a
a Fuse F1U
b Fuse F2U
c Fuse F3U
Blown fuse on the main PCB?
Yes
No
Prerequisite: First perform all earlier main PCB checks, see
4
procedures" [
 84].
1 Turn ON the power of the unit.
Action
No further actions required.
Return to
"Checking
of the PCB and continue with the next
procedure.
b
Action
Replace the main PCB, see
4
procedures" [
 89].
Return to
"Checking
of the main PCB and continue with the
next procedure.
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
"5.2  Wiring
4
procedures" [
 84]
"Checking
"Repair
4
procedures" [
 84]
"Checking
Split Sensira R32
ESIE18-12E – 2021.02