To perform a position check of the 4-way valve
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
12 With the 4‑way valve connector connected to the PCB, measure the voltage
on the 4‑way valve connection of the PCB.
Result: The measured voltage MUST be:
Class
Class 20~42
Class 50~71
Is the measured voltage correct?
Yes
No
1 First perform an electrical check of the 4‑way valve, see
4
procedures" [
 37].
When outdoor temperature is mild and unit can switch between heating and
cooling
INFORMATION
This procedure is ONLY possible when the outdoor temperature is within the
temperature range for both Heating and Cooling operation mode. See the
databook on Business Portal for the temperature range of the operation modes.
2 Activate Heating operation via the user interface.
INFORMATION
It is recommended to connect the service monitoring tool to the unit and verify the
operation mode of the 4-way valve.
3 Check with a contact thermometer (or by touching) if the flow through the 4-
way valve corresponds with the flow shown in the flow diagram. (See
"5.3 Piping
diagram" [
Is the flow correct?
Yes
No
4 Connect a manifold to one of the service ports of the refrigerant circuit and
check the pressure (suction, discharge). Compare with normal operation
conditions of the unit.
Voltage
12 V DC when operating in Heating
mode
0 V DC when operating in Cooling
mode
220~240 V AC when operating in
Heating mode
0 V AC when operating in Cooling
mode
Action
Perform a position check of the 4-way
valve, see
procedures" [
Perform a check the main PCB, see
"2.8 Main
4
 151]).
Action
Skip the next step of this procedure.
Perform the next step of this procedure.
2
Components
|
"2.1.1 Checking
4
 37].
4
PCB" [
 74].
"2.1.1  Checking
Service manual
39