To check for objects that may block the airflow
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
Is the outdoor temperature within the
operating range?
Yes
No
1 Check for the presence of object(s) near the indoor unit that may block the
airflow. Remove the object(s) as needed.
Is the problem solved?
Yes
No
3
Third party components
|
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Wait for the outdoor temperature to
return within the operating range.
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Service manual
137