To install a fuse on the main PCB
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Remove the fuse from the PCB.
a
a Fuse
2 To install a fuse on the main PCB, see
WARNING
For continued protection against risk of fire, replace only with same type and rating
of fuse.
1 Install the fuse on the correct location on the PCB.
CAUTION
Make sure the fuse is plugged‑in correctly (contact with the fuse holder).
a
a Fuse
Is the problem solved?
Yes
No
2
|
"2.10 Plate
work" [
4
"Repair
procedures" [
 81].
Action
No further actions required.
Return to
"Checking
procedures" [
of the PCB and continue with the next
procedure.