H2: Digital Outputs - YASKAWA GA500 Series Programming

Industrial ac microdrive
Table of Contents

Advertisement

1.10 H: Terminal Functions
Setting Value
Function
7E
Reverse Rotation
Identifier
90 - 96
DWEZ Digital Inputs 1 to
7
9F
DWEZ Disable
101 to 19F
Inverse Input of 1 to 9F

H2: Digital Outputs

No.
Name
(Hex.)
H2-01
Term MA/MB-MC
Function Selection
(040B)
H2-02
Term P1-C1 Function
Selection
(040C)
H2-03
Term P2-C2 Function
Selection
(040D)
H2-06
Watt Hour Output Unit
Selection
(0437)
H2-07
Modbus Register 1
Address Select
(0B3A)
H2-08
Modbus Register 1 Bit
Select
(0B3B)
H2-09
Modbus Register 2
Address Select
(0B3C)
H2-10
Modbus Register 2 Bit
Select
(0B3D)
H2-20
Comparator 1 Monitor
Selection
(1540)
H2-21
Comparator 1 Lower
Limit
(1541)
H2-22
Comparator 1 Upper
Limit
(1542)
54
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Set the motor rotation direction when you use Simple Closed Loop V/f Control method.
ON : Reverse run
OFF : Forward run
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets digital inputs used with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of the DriveWorksEZ program saved in the drive.
ON : No
OFF : Yes
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Digital input] to enable this function.
Sets the function of the selected MFDI to operate inversely. To select the function, enter "1xx", where the "xx" is the
function setting value.
Note:
You cannot use inverse input for all functions. Refer to
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function set for MFDO terminal MA-MC or MB-MC.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function for MFDO terminal P1-C1.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function for MFDO terminal P2-C2.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection
= Watt Hour Pulse Output].
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For
example, set H2-20 = 102 to monitor U1-02 [Output Frequency].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the lower limit detection level for comparator 1 when the full scale analog output for
the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the upper limit detection level for comparator 1 when the full scale analog output for
the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
Description
Table 2.49
for more information.
Description
YASKAWA TOEPYAIGA5002A GA500 Programming
Ref.
308
308
309
309
Default
Ref.
(Range)
E
311
(0 - 1FF)
0
311
(0 - 1FF)
2
312
(0 - 1FF)
0
312
(0 - 4)
0001
312
(0001 - 1FFF)
0000
312
(0000 - FFFF)
0001
313
(0001 - 1FFF)
0000
313
(0000 - FFFF)
102
313
(000 - 999)
0.0%
313
(0.0 - 300.0%)
0.0%
313
(0.0 - 300.0%)