H2: Digital Outputs - YASKAWA HV600 Technical Reference

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

5.7 H: Terminal Functions
188 and 1A8: Inverse Inputs of 88 and A8
Setting Value
Function
188 and 1A8
Inverse Inputs of 88 and A8
For example, to use the inverse input of 88 [Thermostat Fault], set H1-xx = 188.

H2: Digital Outputs

H2 parameters set the MFDO terminal functions.
H2-01 to H2-03 Terminal M1-M2, M3-M4, M5-M6 Function Selection
The drive has three MFDO terminals.
No.
H2-01
Term M1-M2 Function Selection
H2-02
Term M3-M4 Function Selection
H2-03
Term M5-M6 Function Selection
Refer to
Table 5.40
to set H2-xx [MFDO Function Selection].
Setting Value
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User-Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
9
Frequency Reference from Keypad
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
*1
F
Not Used
10
Alarm
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During reverse
274
Sets the function of the selected MFDI to operate inversely. To select the function for inverse input, enter two digits of 88 or A8 for
the "xx" in "1xx".
Table 5.39
shows the default function settings for the terminals.
Table 5.39 MFDO Terminals Default Function Settings
Name
Table 5.40 MFDO Setting Value
Function
Reference
Description
Default
0
1
2
Setting Value
280
1B
During Baseblock (N.C.)
280
1E
Executing Auto-Restart
280
1F
Motor Overload Alarm (oL1)
281
20
Drive Overheat Pre-Alarm (oH)
281
21
Safe Torque OFF
282
2F
Maintenance Notification
282
37
During Frequency Output
283
38
Drive Enabled
283
39
Watt Hour Pulse Output
283
3A
Drive Overheat Alarm
283
3D
During Speed Search
283
42
Pressure Reached
283
4C
During Fast Stop
283
4D
oH Pre-Alarm Reduction Limit
284
51
Sequence Timer 1
284
52
Sequence Timer 2
284
53
Sequence Timer 3
284
54
Sequence Timer 4
284
58
UL6 Underload Detected
285
60
Internal Cooling Fan Failure
285
62
Modbus Reg 1 Status Satisfied
286
63
Modbus Reg 2 Status Satisfied
286
69
External Power 24V Supply
286
6A
Data Logger Error
286
71
Low PI2 Control Feedback Level
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Function
During Run
Zero Speed
Speed Agree 1
Function
Reference
287
287
287
287
287
288
288
288
288
289
289
289
289
289
289
289
290
290
290
290
290
290
290
290
290