H2: Digital Outputs

No.
Name
(Hex.)
H2-01
Term M1-M2 Function
Selection
(040B)
H2-02
Term M3-M4 Function
Selection
(040C)
H2-03
Term M5-M6 Function
Selection
(040D)
H2-06
Watt Hour Output Unit
Selection
(0437)
H2-07
Modbus Register 1
Address Select
(0B3A)
H2-08
Modbus Register 1 Bit
Select
(0B3B)
H2-09
Modbus Register 2
Address Select
(0B3C)
H2-10
Modbus Register 2 Bit
Select
(0B3D)
H2-40
Mbus Reg 15E0h bit0
Output Func
(0B58)
H2-41
Mbus Reg 15E0h bit1
Output Func
(0B59)
H2-42
Mbus Reg 15E0h bit2
Output Func
(0B5A)
H2-60
Term M1-M2 Secondary
Function
(1B46)
Expert
H2-61
Terminal M1-M2 Logical
Operation
(1B47)
Expert
H2-62
Terminal M1-M2 Delay
Time
(1B48)
Expert
H2-63
Term M3-M4 Secondary
Function
(1B49)
Expert
H2-64
Terminal M3-M4 Logical
Operation
(1B4A)
Expert
H2-65
Terminal M3-M4 Delay
Time
(1B4B)
Expert
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the function for MFDO terminal M1-M2.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function for MFDO terminal M3-M4.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function for MFDO terminal M5-M6.
Note:
When you do not use this terminal, or when you will use the terminal in through mode,
set this parameter to F.
V/f
OLV/PM EZOLV
OLV/PM
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection
= Watt Hour Pulse Output].
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
V/f
OLV/PM
OLV/PM EZOLV
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV/PM
OLV/PM EZOLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV/PM EZOLV
OLV/PM
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV/PM EZOLV
OLV/PM
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV/PM
OLV/PM EZOLV
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).
V/f
OLV/PM
OLV/PM EZOLV
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).
V/f
OLV/PM EZOLV
OLV/PM
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).
V/f
OLV/PM
OLV/PM EZOLV
Sets the second function for terminal M1-M2. Outputs the logical calculation results of the
terminals assigned to functions by H2-01 [Term M1-M2 Function Selection].
V/f
OLV/PM EZOLV
OLV/PM
Sets the logical operation for the functions set in H2-01 [Term M1-M2 Function Selection]
and H2-60 [Term M1-M2 Secondary Function].
V/f
OLV/PM EZOLV
OLV/PM
Sets the minimum on time used to output the logical calculation results from terminal M1-
M2.
V/f
OLV/PM EZOLV
OLV/PM
Sets the second function for terminal M3-M4. Outputs the logical calculation results of the
terminals assigned to functions by H2-02 [Term M3-M4 Function Selection].
V/f
OLV/PM
OLV/PM EZOLV
Sets the logical operation for the functions set in H2-02 [Term M3-M4 Function Selection]
and H2-63 [Term M3-M4 Secondary Function].
V/f
OLV/PM
OLV/PM EZOLV
Sets the minimum on time used to output the logical calculation results from terminal M3-
M4.
1.10 H: Terminal Functions
Default
Ref.
(Range)
0
305
(0 - 1FF)
1
305
(0 - 1FF)
2
305
(0 - 1FF)
0
305
(0 - 4)
0001
306
(0001 - 1FFF)
0000
306
(0000 - FFFF)
0001
306
(0001 - 1FFF)
0000
306
(0000 - FFFF)
F
306
(0 - 1FF)
F
306
(0 - 1FF)
F
307
(0 - 1FF)
F
307
(0 - FF)
0
307
(0 - 8)
0.1 s
307
(0.0 - 25.0 s)
F
307
(0 - FF)
0
307
(0 - 8)
0.1 s
307
(0.0 - 25.0 s)
1
59