Mitsubishi Electric FR-V500 Series Instruction Manual page 86

Vector inverter
Hide thumbs Also See for FR-V500 Series:
Table of Contents

Advertisement

6.1.4
How to recover from PU stop error (PS)
(1) Restarting method when stop was made by pressing
(Method of restarting from
1)
After the motor has decelerated to a stop, turn off the STF or STR signal.
2)
Press
twice* to display
MODE
CAUTION
When Pr. 79 = 3, press
MODE
(*For monitor screen) ... Refer to page 28 for details of the monitor display provided by pressing
3)
Press
.
SET
4)
Turn on the STF or STR signal.
REMARKS
• If the reset signal (RES) is provided during operation, the inverter shuts off its output while it is reset, the internal thermal
integrated value of the electronic thermal relay function and the number of retries are reset, and the motor coasts.
• The Pr. 75 value can be set any time. This value does not return to the initial value if parameter (all) clear is executed.
• When the motor is stopped from the PU,
(2) Restarting method when stop was made by pressing
1)
After the motor has decelerated
to a stop, turn off the STF or
STR signal.
2)
Press
.
EXT
.....(Recovery from
3)
Turn on the STF or STR signal.
Alternatively, you can make a restart by making a power-on reset or resetting the inverter using the reset terminal of
the inverter.
REMARKS
• If the reset signal (RES) is provided during operation, the inverter shuts off its output while it is reset, the data of the
electronic thermal relay function and the number of retries are reset, and the motor coasts.
• To make a restart, confirm that the PU is connected and then reset the inverter.
• The Pr. 75 value can be set any time. This value does not return to the initial value if parameter (all) clear is executed.
• When the motor is stopped from the PU, PS is displayed. An alarm output is not provided.
• Since PS is not an inverter error, the inverter can not be reset with
Do not reset the inverter with the start signal input.
Doing so will start the inverter immediately after it has recovered from the error, causing hazard.
indication)
.
three times to display
and
are displayed alternately. An alarm output is not provided.
Speed
Control panel
)
STF
ON
(STR) OFF
Example of stop and restart during external operation
CAUTION
83
STOP
from control panel
RESET
. Then press
to proceed to 3).
STOP
from parameter unit
RESET
EXT
STOP
RESET
STOP
.
RESET
Errors (Alarms)
.
MODE
Time
6