Mitsubishi Electric FR-V500 Series Instruction Manual page 44

Vector inverter
Hide thumbs Also See for FR-V500 Series:
Table of Contents

Advertisement

16bit two's complement
Torque
-327.68% -100%
command
-32768
Hexadecimal
8000H
Decimal
32768
CAUTION
• The internal resolution of the torque command is 0.024% (100/2
• The range of torque setting is from -327.68% to 327.67%. (-400% to 400% when shipped from the factory)
• A negative value can not be input from the control panel DU04-01 and parameter unit PU04V, a value can not be set in 0.01%
increments. The setting range is from 600 to 1400% and setting increments is 1% increments. When the value set from the
CC-Link is read from the PU04V or DU04-01, the value is also converted to 600 to 1400 for display.
4.2.5
Torque command setting
Torque command selection
The figure below shows how to give the torque command in the constant power range (extended function
parameter).
Parameter
Name
Constant power
range torque
803
characteristic
selection
(1) Calibration of torque command terminal 3
Refer to the chart on the right for the relationship
between torque setting input voltage and output
voltage. The torque setting input signal is in
proportion to the output torque. Note that the
motor-developed torque varies with the motor
temperature.
Use Pr. 904 and Pr. 905 to adjust bias/gain of
the terminal 3. (Refer to page 51.)
-50%
-25%
-10000
-5000
-2500
D8F0H
EC78H
F63CH
55536
60536
63036
Torque command
Factory
Setting
Setting
Range
0
0, 1
41
Torque control operation
0%
25%
50%
0000
2500
5000
0
09C4H
1388H
0
2500
5000
12
) and the fraction less than the resolution is rounded off.
Pr. 803 = 1: Constant torque
Pr. 803 = 0: Constant output
Speed
Base speed
Output torque
(Torque command)
150%
-10V
0
-150%
100%
327.67%
10000
32767
2710H
7FFFH
10000
32767
Gain
Pr. 905
Bias
Pr. 904
10V
Terminal 3
4