Function list (Extended function parameters)
Name
DU/PU main display
52
data selection
PU level display data
53
selection
DA1 terminal function
54
selection
Speed monitoring
55
reference
Current monitoring
56
reference
57 Restart coasting time
58 Restart cushion time
Remote setting
59
function selection
Intelligent mode
60
selection
You can select the DU/PU main display data.
0, 100: Speed, output current, output voltage, alarm display
5: Preset speed
6: Output frequency
7: Motor torque
8: Converter output voltage
9: Regenerative brake duty
10: Electronic thermal relay function load factor
11: Output current peak value
12: Converter output voltage peak value
17: Load meter
18: Motor excitation current
19: Position pulse
20: Cumulative energization time
23: Actual operation time
24: Motor load factor
32: Torque command
33: Torque current command
34: Motor output
35: Feedback pulse
38: Trace status
You can select the PU level display data.
0: No monitor
1: Speed
2: Output current
3: Output voltage
5: Preset speed
6: Output frequency
7: Motor torque
8: Converter output voltage
9: Regenerative brake duty
10: Electronic thermal relay function load factor
11: Output current peak value
12: Converter output voltage peak value
17: Load meter
18: Motor excitation current
You can select the monitor output DA1 data.
1: Speed
2: Output current
3: Output voltage
5: Preset speed
6: Output frequency
7: Motor torque
8: Converter output voltage
9: Regenerative brake duty
10: Electronic thermal relay function load factor
11: Output current peak value
12: Converter output voltage peak value
17: Load meter
18: Motor excitation current
21: Reference output
32: Torque command
33: Torque current command
34: Motor output
36: Torque monitor (driving/regenerative polarity switching)
You can set the reference value of speed monitoring.
0 to 3600r/min
You can set the reference value of current monitoring.
0 to 500A
When power is restored after an instantaneous power failure, you can start the inverter
without stopping the motor (in a coasting status). When this time (Pr. 57) elapses after
power was restored, the inverter begins to restart.
When you set "9999", the inverter will not restart. Generally, setting of "0" does not
pose a problem, but the time can be adjusted (0, 0.1 to 5s, 9999) according to the
magnitude of the load.
When the restart coasting time (Pr. 57) elapses, the output voltage is risen gradually.
Set this cushion time (Pr. 58) (0 to 60s).
Normally, you can perform operation with the factory settings, but you can adjust them
according to the load magnitude. (Pr. 58 is valid only during V/F control)
You can make remote setting of the speed when the control panel is located away from
the control box.
0: None
1: With remote setting function, with frequency setting storage function
2: With remote setting function, without frequency setting storage function
3: With remote setting function, without frequency setting storage function
(Turning STF/STR off clears remote setting)
Set when using the brake sequence control.
0: Normal operation mode
7: Brake sequence mode
(With mechanical brake opening completion signal input)
8: Brake sequence mode
(Without mechanical brake opening completion signal input)
Outline
60
At-a-glance Guide to
Functions
: Usable function
× : Unusable function
Cus-
* : Functions that can be used
Factory
tomer
for parameter-set position
Setting
Set-
control
ting
Vector Control
Speed
Torque
control
control
0
1
1
1500r/min
Rated
inverter
current
9999
×
×
1.0s
0
×
0
Position
control
×
×
×
×