Mitsubishi Electric FR-V500 Series Instruction Manual page 11

Vector inverter
Hide thumbs Also See for FR-V500 Series:
Table of Contents

Advertisement

Connection diagram, encoder cable,
PU connector
2.2.2
Main circuit terminal specifications
(1) Specification of main circuit terminal
Terminal Symbol
Terminal Name
R, S, T
AC power input
U, V, W
Inverter output
Power supply for
R1, S1
control circuit
Brake resistor
P, PR
connection
Brake unit
P, N
connection
DC reactor
P, P1
connection
Built-in brake circuit
PR, PX
connection
Earth (Ground)
CAUTION
• The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never
perform such wiring.
• When connecting the dedicated external brake resistor (FR-ABR), remove jumpers across terminals
PR-PX (5.5K or less).
Set "1" in Pr. 30 "regenerative function selection".
Set Pr. 70 "special regenerative brake duty" as follows:
7.5K or less . . . . . . . . 10%
11K or more . . . . . . . 6%
Refer to the Instruction Manual (detailed) for details.
• When connecting the brake unit (FR-BU, BU type), remove jumpers across terminals PR-PX (5.5K or
less). Refer to the Instruction Manual (detailed) for details.
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter (FR-
HC) or power regeneration common converter (FR-CV).
Connect a three-phase squirrel-cage motor or Mitsubishi dedicated motor.
Connected to the AC power supply terminals R and S. To retain the alarm
display and alarm output or when using the high power factor converter (FR-
HC) or power regeneration common converter (FR-CV), remove the jumpers
from terminals R-R1 and S-S1 and apply external power to these terminals.
Do not turn off the power supply for control circuit (R1, S1) with the main
circuit power (R, S, T) on. Doing so may damage the inverter. The circuit
should be configured so that the main circuit power (R, S, T) is also turned off
when the power supply for control circuit (R1, S1) is off.
15K or less: 60VA, 18.5K to 55K: 80VA
Disconnect the jumper from terminals PR-PX (5.5K or less) and connect the
optional brake resistor (FR-ABR) across terminals P-PR.
For the 15K or less, connecting the resistor further provides regenerative
braking power.
Connect the optional FR-BU type brake unit, BU type brake unit, power
regeneration common converter (FR-CV) or high power factor converter
(FR-HC).
Disconnect the jumper from terminals P-P1 and connect the optional DC
reactor (FR-HEL/BEL).
When the jumper is connected across terminals PX-PR (factory setting),
the built-in brake circuit is valid. (Provided for the 5.5K or less.)
For earthing (grounding) the inverter chassis. Must be earthed (grounded).
8