Mitsubishi Electric FR-V500 Series Instruction Manual page 29

Vector inverter
Hide thumbs Also See for FR-V500 Series:
Table of Contents

Advertisement

Basic operation (Speed setting, run,
speed meter adjustment)
3.2.2
Adjustment (calibration) of speed meter (meter)
Changing example
POINT
• Pr. 900 "DA1 terminal calibration" can be read by setting "1" (extended function parameter enable) in
Pr. 160 "extended function selection".
• Set Pr. 900 "DA1 terminal calibration".
• Set any of "1 to 3, 5 to 12, 17, 18, 21, 32 to 34 and 36" in Pr. 54 "DA1 terminal function selection" to
output a signal to the terminal DA1. (Refer to page 60)
Press
to operate the inverter. (It is not necessary to
1.
FWD
connect a motor.)
2.
Press
to select the parameter setting mode.
MODE
3.
Display the present running speed by pressing
read Pr. 900.
4.
Press
or
to adjust the meter pointer to
a predetermined position. (Depending on the setting,
it may take some time until the pointer moves.)
REMARKS
1. Pressing
to start reverse rotation operation will move the
REV
meter pointer reversely (in the negative direction).
2. The terminal DA1 output will also keep displaying the monitor
when the inverter stops due to an alarm.
5.
Press
for about 1.5s.
SET
This completes the setting.
STOP
Press
to stop the inverter.
6.
RESET
CAUTION
1. When the speed meter is connected across terminals DA1-5 to monitor the speed, the output of
terminal DA1 is saturated if the maximum output speed reaches or exceeds 1500r/min, with the
factory setting unchanged. Hence, the setting of Pr. 55 "speed monitoring reference" must be
changed to the maximum output speed. (Refer to page 60.)
2. Terminal DA2 can be adjusted in Pr. 901
3. For operation from the parameter unit (FR-PU04V), refer to the instruction manual of the FR-PU04V.
REMARKS
• For monitor display changes by
• Calibration can be made also during external operation.
At the preset speed of 1500r/min, make adjustment so that the meter (analog meter)
deflects to full-scale. Calibrate the DA1 terminal (±10V).(in PU operation mode)
Operation
, refer to page 28.
MODE
MODE
to
SET
SET
26
Display
FR-DU04
CONTROL PANEL
-1
Hz¤r
A
V
MON
EXT
PU
REV
FWD
(Analog voltage meter)
Flicker ...
Parameter setting complete!!