Function list (Simple mode parameters)
The inverter operation mode can be changed as desired between operation using external signals (external
operation), operation from the PU (FR-DU04
operation (external/PU combined operation), and computer link operation (when the FR-A5NR option is used).
Pr. 79 Setting
At power-on, the inverter is placed in the external operation mode.
0
Operation can be performed by switching between PU and external operation.
1
PU operation mode
2
External operation mode
External/PU
3
combined
operation mode 1
External/PU
4
combined
operation mode 2
Switchover mode
6
Switchover between PU operation, and external operation, and computer link operation (when the FR-
A5NR or any other communication option is used) can be done while running.
External operation mode (PU operation interlock)
7
X12 signal ON..........May be switched to PU operation mode (output stop during external operation)
X12 signal OFF ........Switching to PU operation mode inhibited
Operation mode switching by the external signal (disallowed during operation)
8
X16 signal ON..........Switched to external operation mode
X16 signal OFF ........Switched to PU operation mode
Refer to the Instruction Manual (detailed) for details.
Refer to page 50 for details.
Set this parameter to display/set the extended function parameters.
REMARKS
Refer to page 58 for the parameters (extended function parameters) available when "1" is set in Pr. 160 "extended function
display selection".
Pr. 79 "operation mode selection"
/FR-PU04V), combined operation of PU operation and external
-1
Speed command
Set from the PU (FR-DU04
(direct setting,
signal input (multi-speed setting only)
Speed command
External signal input (terminal 2, 1, jog,
multi-speed selection)
Pr. 95 "online auto tuning selection"
Pr. 160 "extended function display selection"
Setting
0
Only the simple mode parameters are displayed.
1
All parameters are displayed.
Function
Start command
/FR-PU04V)
-1
External signal input (terminal STF, STR)
) or external
Start command
Input from the PU (FR-DU04
(start command using
Description
56
/FR-PU04V)
-1
,
)
FWD
REV