Siemens SIMATIC 6ES7673-2CC40-0YA0 Hardware Installation And Operating Manual page 32

Windows automation center winac slot version 4.0
Table of Contents

Advertisement

Restart Behavior of the CPU 41x-2 PCI after Power On of PC
The restart behavior of the CPU 41x-2 PCI after Power On varies according to how
you connected the CPU 41x-2 PCI to the power supply. The restart behavior of the
CPU 41x-2 PCI after Power On of the PC depends on several factors:
Whether or not backup battery is available
Whether or not the CPU 41x-2 PCI is connected to an external independent
power supply (UPS)
Type of memory card (FLASH card or RAM card)
Independent
24 VDC
power supply
No
No
Yes
Windows Automation Center, WinAC Slot Version 4.0
Hardware Installation and Operating Manual, Edition 02/2006, A5E00273194-02
Installing the CPU 41x-2 PCI and the Software
Backup
What happens after a Power Off/Power On of the
battery
PC?
When the PC is powered off, the CPU 41x-2
No
loses its power supply - a backup battery is not
available, and the user program is aborted.
A user program on the FLASH card is retained.
All RAM contents (work and integrated load
memory, RAM card) are lost.
After the PC is powered on, the mode selector is
on STOP and the CPU 41x-2 PCI performs an
automatic memory reset and remains in STOP
mode (cold restart).
Yes
When the PC is powered off, the CPU 41x-2 PCI
rescues the necessary data and goes to STOP
mode in order to be ready for restart. RAM
contents are retained.
After the PC is powered on, the CPU 41x-2 PCI
performs a warm restart/hot restart/cold restart or
remains in STOP mode, depending on the
parameter assignment and the mode selector
setting.
The CPU 41x-2 PCI continues running in spite of
Yes/No
Power On/Power Off of PC.
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic 6es7673-6cc40-0ya0

Table of Contents