Siemens SIMATIC 6ES7673-2CC40-0YA0 Hardware Installation And Operating Manual page 124

Windows automation center winac slot version 4.0
Table of Contents

Advertisement

Pulse-Shaped Interferences
The following table presents the electromagnetic compatibility of modules with
respect to pulse-shaped interferences. This presupposes that the system complies
with the specifications and guidelines on electrical installation.
Pulse-Shaped Interference
Electrostatic discharge in
accordance with
IEC 61000-4-2
Burst pulses in accordance with
IEC 61000-4-4
High-energy surge in
accordance with IEC 61000-4-5
Asymmetrical interference
Symmetrical interference
Sinusoidal Interferences
The following table presents the EMC behavior with respect to sinusoidal
interferences:
Sinusoidal
Interference
HF radiation
(electromagnetic fields)
in accordance with IEC
61000-4-3
Conducted RF
interference on cables
and cable shields in
accordance with IEC
61000-4-6
Emission of Radio Interferences
Radio interference in accordance with EN 55022: Limit Class B.
Performing Work on the Prod
To protect the product from discharge of static electricity, operating personnel must
take appropriate action to discharge static electricity from their bodies prior to
touching the module.
Windows Automation Center, WinAC Slot Version 4.0
Hardware Installation and Operating Manual, Edition 02/2006, A5E00273194-02
Tested with
Air discharge: ± 8 kV
Contact discharge: ± 6 kV
2 kV
2 kV (supply line) DC voltage with
protectors
2 kV (data line)
1 kV (supply line) DC voltage with
protectors
Tested with
10 V/m with 80% amplitude
modulation of 1 kHz over the range
of 80 MHz to 1000 MHz and 1,4 GHz
to 2 GHz
Test voltage of 10 V with 80%
amplitude modulation of 1 kHz over
the range of 10 KHz to 80 MHz
Reference Information
Correspond-
ing Severity
3
3
3
Corresponding
Severity
3
3
123

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic 6es7673-6cc40-0ya0

Table of Contents