5.5.3 Panel Settings
General NCA-2 preferences can be set from this program screen.
LOCAL CONTROL - Press this soft key to toggle between Yes and No. This option disables (No) or enables (Yes) local panel
control of the Signal Silence, System Reset, and Drill (Alarm Signal for Canadian applications) Fixed Function keys, as well as
SIGNAL SILENCE, SYSTEM RESET, and ACKNOWLEDGE soft keys. A setting of No (disable) turns the panel piezo sounder
off, overriding the next field if PIEZO is set to ON. Default: Yes.
PIEZO - Press to toggle between Off and On. This option enables (On) or disables (Off) the panel piezo from sounding when
alarms or troubles occur. Default: On.
DISPLAY ADDRESS - Selecting NO instructs the NCA-2 not to
display the node and point in the event at the top of the screen.
Selecting YES displays all node and point information defined from
the NCA-2 Node Program menu options.
EVENT ORDERING - Switches between USA and CANADA
ordering. USA priority events come in on the Event Counts screen
and Canada priority events come in on the Multiple Event List
screen.
REMINDER MENU - These reminders occur daily at 11:00 AM
(not configurable). Local reminders restart the NCA-2 piezo and
require re-acknowledgment of the events. Proprietary reminders re-
send trouble messages across the network. Remote reminders cause
connected ACS devices to re-display the conditions.
Note: Alarm, Supervisory, and CO Event reminder programming
available via VeriFire Tools.
68
N E T W O R K M A P P I N G
S C R E E N 0 1 O F 1 5
0 0 1 : O F F L I N E /
0 0 3 : O N L I N E
/ M A P P E D 0 0 4 : O F F L I N E /
0 0 5 : O F F L I N E /
0 0 7 : O F F L I N E /
0 0 9 : O N L I N E
/ M A P P E D 0 1 0 : O F F L I N E /
0 1 1 : O F F L I N E /
0 1 3 : O F F L I N E /
0 1 5 : O F F L I N E /
A U T O P R O G R A M
N E X T
Figure 5.24 Program Menu: Network Mapping
0 0 2 : O F F L I N E /
0 0 6 : O F F L I N E /
0 0 8 : O F F L I N E /
0 1 2 : O F F L I N E /
0 1 4 : O F F L I N E /
0 1 6 : O F F L I N E /
With Fire as the highest
priority:
USA Event
Canada
Order
Event Order
Fire
Fire
CO Alarm
CO Alarm
MN Alarm
CO Pre-alarm
CO Pre-alarm
Security
Supervisory
Supervisory
MN Supervisory
Trouble
Trouble
MN Trouble
Pre-alarm
Pre-alarm
Disabled
Disabled
N t
Fi /MNS
i it d
NCA-2 Manual — P/N 52482:M5 03/20/2019
Panel Program Menu
A C C E P T
B A C K
With MNS as the highest
priority:
USA Event
Canada
Order
Event Order
MN Alarm
Fire
Fire
CO Alarm
CO Alarm
CO Pre-alarm
CO Pre-alarm
Security
MN
Supervisory
Supervisory
Supervisory
MN Trouble
Trouble
Trouble
Pre-alarm
Pre-alarm
Disabled
Disabled
d
t
i