F.1: Conversions Common To Ul 8Th Edition Panels; F.2: Am2020/Afp-1010 - Honeywell NOTIFIER NCA-2 Instruction Manual

Network control annunciator
Hide thumbs Also See for NOTIFIER NCA-2:
Table of Contents

Advertisement

The NCA-2 is compatible with the FACPs in this appendix that have software as described in Table F.1. Display differences and pro-
gramming requirements are noted in each section.
Use of the NCA-2 with these FACPs is subject to AHJ approval. Refer to "UL 864 Compliance" on page 8.
F.1 Conversions Common to UL 8th Edition Panels
Device Trouble Types
Device trouble types for the AFP-200, AFP-300/400,and AM2020/AFP-1010 FACPs will be displayed on the NCA-2 as follows:
Detector Sensitivity
NCA-2 screens that display detector sensitivity translate the AFP-200, AFP-300/400, and AM2020/AFP-1010FACP levels as follows:
F.2 AM2020/AFP-1010
Device Point Types
The device types for this panel will display according to the NCA-2 in Table F.4.
NCA-2 Manual — P/N 52482:M5 03/20/2019
Appendix F: UL 8th Edition Panel Applications
FACP
AFP-200
AFP-300, AFP-400
AM2020, AFP-1010
Table F.1 Software Compatibility
FACP Device Trouble
Invalid Reply
Low Chamber Value < 20% of alarm level
Maintenance required > 80% of alarm level
Sensitivity High
Sensitivity Low
Open Circuit
Short Circuit
Point Trouble
Detector Failed Chamber Test
Drift Compensation Error
Verification Count Overflow
Security Tamper
Security Invalid Reply
Table F.2 NCA-2 Device Trouble Display
FACP Sensitivity Level
Low Sensitivity
Medium Sensitivity
High Sensitivity
Table F.3 NCA-2 Detector Sensitivity Display
AFP-1010/AM2020
Device Point Type
HEAT(ANALOG)
FIXED THER D
MON NORM CLD
SPRNKLR MNTR
FORM C RELAY
POWER(CONV)
Table F.4 NCA-2 Display for AM2020/AFP-1010 Device Point Types
Compatible with NCA-2 at Software Level:
Rev. 3.02 or greater
Rev. 3.65 or greater
SIB, DIA, CPU Rev. 4.0 or greater
NCA-2 Displays:
No Response
Low Threshold
Maintenance Alert
Maintenance Alert
Maintenance Alert
Open Circuit
Short Circuit
General Trouble
Detector Failed Test
Maintenance Alert
Verify Count Over 20
Security Tamper
No Response
NCA-2 Displays Sensitivity Level:
NCA-2 Displays:
HEAT
HEAT(FIXED)
NC MONITOR
SPRINKLER SYS
RELAY
CONTROL
9
5
1
AFP-1010/AM2020
NCA-2 Displays:
Device Point Type
TROUBLE
GEN TROUBLE
TROUBLE FORC
GEN TROUBLE
FIXED PHOT D
SMOKE(PHOTO)
PAGE
MON PULL STA
MONITOR PAGE
TELE PAGE
PULL STATION
TELE PAGE
95