Programming
Main menu
Program/alter status
Alter status
Clear verify counters
NOTE: For
remote nodes
only.
5.3.5 Clear History
Select Clear History from the Alter Status Main Menu, then choose NCA-2 HISTORY or NODE HISTORY N
igate to the Clear History menu, where there are three options: ALARM HISTORY, which clears only the alarm history buffer, EVENT
HISTORY, which clears only non-alarm events in the history buffer, and ALL HISTORY, which clears both the alarm buffer and the
event buffer. Once you clear a history buffer, the data is not recoverable. BACK or <ESC> will return the user to the Alter Status menu.
Refer to Figure 5.11 on page 60.
NOTE: For use with NFS-320, NFS2-640, and NFS2-3030 nodes.
Main menu
Program/alter status
Alter status
Clear NCA History
NOTE: Node
history options are
ALARM HISTORY
or ALL HISTORY.
5.3.6 Walk Test
When connected to an FACP that supports the function (e.g. NFS2-640 and NFS2-3030), the NCA-2 walk test allows you to remotely
test all active alarms on the monitoring network. There are two types of tests: Basic and Advanced. The advanced test allows you to
retain Control-By-Event (CBE) and Cooperative-Control-By-Event (CCBE) actions.
NOTE: Network zones and network logic zones may be used as part of a logic equation; network trouble zones may be used as part of a
trouble equation. CCBE (Cooperative Control-by-event) is the term used to refer to programming over the network in this manner.
To perform a walk test, select the corresponding option from the Alter Status menu.
BASIC/ADVANCED - Toggles between the basic and advanced Walk Test. When ADVANCED is selected, there is an END TEST
option. END TEST is not an option for the basic test.
SILENT/AUDIBLE - future use.
60
T R O U B L E
P R O G M O D E A C T I V A T E D
N O D E L A B E L F O R L O C A L N C A - 2
1 0 : 4 8 : 5 2 A T U E J A N 2 2 , 2 0 1 9
C L E A R V E R I F Y C O U N T E R S
N O D E A D D R E S S :
T H I S W I L L C L E A R A L L V E R I F Y C O U N T E R S
C L E A R C O U N T E R S
Figure 5.10 Alter Status - Clear Verify Counters
T R O U B L E
P R O G M O D E A C T I V A T E D
N O D E L A B E L F O R L O C A L N C A - 2
1 0 : 4 8 : 5 2 A T U E J A N 2 2 , 2 0 1 9
C L E A R N C A H I S T O R Y
A L A R M H I S T O R Y
E V E N T H I S T O R Y
A L L H I S T O R Y