Programming
• The status light is never on.
• Pressing the button attempts to drill the single node.
5.
DISABLE
• The State light is on if the corresponding point or zone is active.
• The status light is on if the corresponding point or zone is disabled. Note that for most panels, the state light will not be on when
the point is disabled (however, this can vary in different panels).
• Pressing the button will modify the state of the point or zone as follows:
-If the point is enabled, pressing the button will disable it.
-If the point is disabled, pressing the button will enable it.
6.
MONITOR
• The State light is on if the corresponding point or zone is active.
• The status light is on if the corresponding point or zone is in trouble.
• Pressing the button has no effect.
7.
CONTROL
• The State light is on if any of the corresponding points or zones are active.
• The status light is on if any of the corresponding points or zones are in trouble. The light will also be on if any of the points in the
group fail to activate.
• Pressing the button will modify the state of the point or zone as follows:
-If the point or zone is currently active, pressing the button will deactivate it
-If the point or zone is currently inactive, pressing the button will activate it
NOTE: Attempts to change the state of a point or zone in this manner may be overridden by some system settings, such as a panel auto-
silencing an output after a certain amount of time, or CBE equations based on events at another network node.
8.
ALL CALL - The node number is a specific node:
• The state light is on if the node has entered the all call state.
• If Node 0 is selected, the state light is on if any of the nodes are active.
9.
PAGE INACTIVE, PAGE EVAC, PAGE ALERT
• The state light is on when the program function is active.
• The status light is on if the point is in trouble.
10. TELEPHONE
• Both lights will flash if a telephone has just been placed in the jack. Otherwise, the State light is on if the corresponding point or
zone is active.
• The status light is on if the corresponding point or zone is in trouble.
• Pressing the button will activate or deactivate the telephone circuit.
11. SHADOW
• Lights on the ACS points will shadow (mimic) the lights on the mapped ACS point, except any flashing sequence may be
different.
12. PAGE
• Intended for DVC, not LED annunciators; the state and status light are not applicable.
5.5.7 Supervision
The Supervision screen allows you to make supervision settings for various ancillary devices. The EIA-232 and EIA-485 ports are unsu-
pervised, but a programmed NCA-2 will detect loss of communication with the device(s) on these circuits.
MAIN PS NODE: - To enable supervision of the NCA-2's main power supply, enter the node number where the power supply is
located. If the NCA-2. is powered by its own power supply, the node number will be the same as the NCA-2's. node number. If
power supply supervision is not desired, enter
PRINTER: - Press to scroll through the types of printer supervision:
COLUMN
80 COLUMN SUPERVISED
,
be active if
NONE
CRT BAUD RATE
4800 SUP
9600
,
AUXILIARY TROUBLE REPORTING: - Press to toggle between
attached at J5. Default:
TAMPER INPUT: - Selections are
YES/NO
tamper switch. Section 3.17, "Security Tamper Switch" provides installation information.
AKS-1
should be selected when using an AKS-1 key switch connected to the panel cabinet door (which allows the operator
to use Signal Silence, Reset, Drill (Alarm Signal for Canadian applications) and Acknowledge functions when a key turns the
lock to "Enable). Section 3.16 provides installation instructions.
MORE - Select
78
40 GRAPHIC
,
is selected. If a
SUPERVISED
:
Press to scroll through CRT baud rates. "
9600 SUP
19200
19200 SUP
,
,
,
NO
YES
NO
,
YES
reports (
) or does not report (
MORE
to bring up the second supervision screen.
000
000
. Default =
.
NONE
80 GRAPHIC
,
selection is made, the printer will be supervised. Default =
SUP
" after the rate indicates supervised. Select from:
38400
38400 SUP
,
,
YES
and
AKS-1
NO
, and
. Default =
.
NO
) a tamper situation at the panel cabinet door (as determined by an STS-1
40 COLUMN
40 COLUMN SUPERVISED
,
,
80 GRAPHIC SUPERVISED
,
57600
57600 SUP
,
,
NO
YES
. Choose
if a trouble bus cable has been
NCA-2 Manual — P/N 52482:M5 03/20/2019
Panel Program Menu
80
,
. The printer will not
NONE
.
4800
,
NONE
. Default: