Programming
Panel Settings 2 (MORE) Menu
Pressing M O R E at the Panel Settings screen brings up the following screen.
Main menu
Program/alter status menu
Panel Program menu
Panel settings
More
MN Control - Press to toggle between SUBSIDIARY, ACU, LOC, and CCS. Set this option to subsidiary if the NCA-2 does not have an
associated DVC set as an ACU, LOC or CCS. Select ACU, LOC, or CCS for this option to match the configuration programming of an
associated DVC used for Mass Notification.
MN Priority Over Fire - Press to toggle between YES, NO and MN NOT USED. If the MN PRIORITY OVER FIRE option is set to
NO, Fire events will have a higher priority than Mass Notification (MN) events. If set to YES, MN events will have a higher priority than
Fire events. If set to MN NOT USED, this system is being used for fire protection only. Refer to Event Ordering on page 68.
NOTE: For network applications, the MN Priority Over Fire setting should be set the same for each applicable node.
DCC Participation - Toggles the Display & Control Center supervision between YES and NO. See Appendix D, "Display and Control
Center (DCC)"for details.
CAUTION: DCC PARTICIPATION
!
ON SYSTEM UTILIZING THE DCC FUNCTION, ALL LOCATIONS THAT CAN PARTICIPATE IN DCC SHOULD BE SET
TO YES.
Regional Settings - Press this soft key to proceed to the Regional Settings screen.
SCS Settings - Press this soft key to proceed to the SCS Settings screen.
Default Settings - Press to activate NCA-2 default settings for the following:
70
P A N E L S E T T I N G S
M N C O N T R O L : S U B S I D I A R Y
M N P R I O R I T Y O V E R F I R E : M N S N O T U S E D
D C C P A R T I C I P A T I O N :
D E F A U L T S E T T I N G S :
Figure 5.27 Panel Settings 2 (MORE)
Program setting for:
Local Control
Piezo
Event Reminder
Event Ordering
Display Address
DCC Participation
Regional Settings
Table 5.2 Programming Defaults
R E G I O N A L S E T T I N G S
S C S S E T T I N G S
N O
Default:
Yes
On
Yes
USA
Yes
No
Default
NCA-2 Manual — P/N 52482:M5 03/20/2019