Honeywell NOTIFIER NCA-2 Instruction Manual page 44

Network control annunciator
Hide thumbs Also See for NOTIFIER NCA-2:
Table of Contents

Advertisement

Operation
This example requests a history of all events on Node one only, Loop one only, for all modules, panel circuits and bell circuits. Since the
start point specifies module device addresses (M001), detectors would not be included in this query as they are first in the device type
order. Figure 4.10 shows how this inquiry would appear on the screen.
Ordering of devices on a node:
1.
Node One, Loop One Detectors, Modules, etc.
2.
Node One, Loop Two Detectors, Modules, etc.
3.
Node One Panel Circuits
4.
Node One Bell Circuits
5.
Node Two, Loop One Detectors, Modules, etc.
6.
Node Two, Loop Two Detectors, Modules, etc.
7.
Node Two Panel Circuits
8.
Node Two Bell Circuits
etc...
NOTE: If the Start and End Point nodes are not consecutive, e.g. the Start Point is Node 1 and the End Point is Node 3 or above, the NCA-
2 will display all event types on all nodes between the Start Point and End Point.
Main menu
History display
Local history
Point range
Node History
When you select this option from the History Select menu (see Figure 4.6 on page 41), you can display or print event details for a speci-
fied node. Enter the node number in the NODE HISTORY N
be on-line, and the node selected must be mapped in the local NCA-2's programming. The choices from the Node History menu are:
ALL EVENTS
ALARMS ONLY
For example, if a user selects ALL EVENTS, a screen similar to that of Figure 4.11 on page 45 will be displayed. In this example, the
first four lines show the System Normal message, the date and the time. The screen specifies the node on which the event or events
occurred, and displays the event counter, which in this instance would show all events in descending date order (from most recent to least
recent). Event details are displayed after the event counter. Details include the event type, node address, node location (which is custom
defined by the operator), device type, and the date and time of the event. The user can scroll through the event history by pressing the
soft keys NEXT EVENT or PREVIOUS EVENT. Pressing the BACK key will return to the History Main menu.
NOTE: For use with NFS-320, NFS2-640, NFS2-3030, and DVC nodes.
44
S T A R T P O I N T :
N 0 0 1 L 0 1 M 0 0 1 ( M O D U L E )
E N D P O I N T :
N 0 0 1 B 1 0 0 ( B E L L C K T )
E V E N T T Y P E : A L L E V E N T S
Figure 4.10 Point Range Select Screen
field, then press the corresponding soft key. The local NCA-2 must
P O I N T R A N G E
NCA-2 Manual — P/N 52482:M5 03/20/2019
The LCD Display
A C C E P T
B A C K

Hide quick links:

Advertisement

Table of Contents
loading