Honeywell NOTIFIER NCA-2 Instruction Manual page 98

Network control annunciator
Hide thumbs Also See for NOTIFIER NCA-2:
Table of Contents

Advertisement

UL 8th Edition Panel Applications
Control ON/OFF on the AFP-200 is not supported.
Shadow Points
Shadow points are not supported on an AFP-200.
MONITOR ACS points can not look at output modules, bell circuits or panel circuits on an AFP-200.
Auto-Acknowledge
A Network Adaptor Module (NAM) connected to an AFP-200 will auto-acknowledge an event on the panel. The panel then shows the
event as acknowledged, and this event can not be acknowledged again at the panel since it has already been acknowledged locally. The
NCA-2 or another display node must be used for acknowledgement.
98
NCA-2 Manual — P/N 52482:M5 03/20/2019
AFP-200

Hide quick links:

Advertisement