Flex 402/Flex 404 Fire Alarm Control Panel - Honeywell FCI Gamewell Flex 404 Instruction Manual

Fire alarm control panels
Table of Contents

Advertisement

NORMAL - Only the GREEN AC POWER LED is on.
All other LEDs are off.
WHEN AUDIBLE DEVICES ARE SOUNDING -
FOR AN ALARM
1. Evacuate the protected area
2. Notify the monitoring service and/or the Fire Department immediately. Tell them briefly what happened and what your current status is.
Phones: ________________________________________
3. If the Fire Department is responding, be prepared to provide directions to arriving firefighters.
FOR TROUBLE ONLY
1. Notify the monitoring service and/or Fire department if this panel is connected to either one, and tell them what is happening.
2. Silence audible devices by unlocking and opening the panel and pressing the ACKNOWLEDGE key for a minimum of one second. The
yellow SYSTEM TROUBLE LED will remain on. Contact authorized service personnel immediately! (See Below).
DO NOT ALLOW TROUBLE CONDITIONS TO REMAIN LOGGED IN THE SYSTEM. THE PROTECTION THE
SYSTEM OFFERS HAS BEEN COMPROMISED OR ELIMINATED, WHEN A TROUBLE CONDITION EXISTS.
To return to normal after an alarm
1. Do not enter the protected area until safe to do so.
2. Clear all initiating devices. Smoke detectors will not reset if there is
still smoke in the area.
3. Reset the control panel (PRESS the RESET key.)
Power failure or brownout
If AC power drops too low or fails, the AC POWER LED will go out, the
SYSTEM TROUBLE LED will turn on, the POWER TROUBLE LED will
turn on, and the panel buzzer and any other audible trouble devices will
sound. Contact authorized service personnel immediately. See below.
In the event of trouble, contact the local
Gamewell/FCI Service Representative
Name: _____________________________________
Company: __________________________________
Address: ___________________________________
Telephone Number: __________________________

Flex 402/Flex 404 Fire Alarm Control Panel

Operating Instructions
Fire Department
WARNING!
PANEL KEY - The key to open the panel can be found at the following
location:
________________________________________________________
_____________________________________________
Monitoring Service
Manual activation (Fire Drill or otherwise)
Notification Appliance Circuits (NACs) can be activated by activating a
manual pull station.
NOTE: You may want to disconnect the municipal box by
sliding the DISCONNECT switch, located on the 4XTMF
module, to its disconnect position (to the right). If a DACT is
connected, notify the monitoring service before conducting
any fire drills or tests.
Alarm Silencing
Notification Appliance Circuits may be silenced by pressing the
ACKNOWLEDGE key and then the ALARM SILENCE key. The ALARM
SILENCE LED will turn on. Subsequent alarms will reactivate circuits.
Press the RESET key to clear the "silenced" condition.
NOTE: Notification Appliance Circuits may be programmed
as nonsilenceable. Also, Signal Silence Inhibit, if enabled,
will prevent silencing of NACs for one minute after an alarm
(see manual).
To test the lamps and piezo sounder
Press and release the RESET key and check all LEDs. Every LED
should be on and the piezo should sound.
For more information, refer to the Flex 402/Flex 404 Series Manual,
Document #52194. It is kept in the following location:
_______________________________________________________
THIS SHEET SHALL BE FRAMED ADJACENT TO THE
CONTROL PANEL
Document #52193
Rev. A1
11/19/10
ECN 10-104