Panel Program Menu
Control mode source field entries may be:
• SLC modules in the format NxxxLyyMzzz. xxx = FACP node number, yy = the SLC loop number, zzz = module SLC address.
• Panel Circuit modules in the format NxxxPyy.z. xxx = FACP node number, yy = panel circuit module number, z = panel circuit
pushbutton number.
• Prioritized Audio Matrix (PAM) speaker points, in the format NxxxIyyyyAzzSn. xxx = the DVC node number, yyyy = the input
number in the PAM, zz = the DAA address on the Digital Audio Loop (01 through 32), and n = the speaker circuit (1 through 4).
• General zones in the format NxxxZyyy.xxx = FACP node number, yyy=General zone number (Z001-Z999), not Z000. Zone 0 is
not valid.
CAUTION: DO NOT MIX GENERAL ZONES WITH OTHER SOURCE TYPES
!
DO NOT MIX GENERAL ZONES WITH OTHER SOURCE TYPES FOR AN ACS CONTROL POINT. PROGRAM UP TO
EIGHT GENERAL ZONES OR UP TO EIGHT OTHER CONTROL POINT TYPES.
For ALL CALL, PAGE INACTIVE, PAGE EVAC, and PAGE ALERT modes, enter the node number of the DVC where the source is
connected. These modes are used in conjunction with ENABLE PAGING FOR ____ mode.
FFT-NFN
mode sources:
• format Nxxx,Nxxx,NxxxLyyMzzz: Telephone control module (NxxxLyyMzzz) preceded by the node numbers of the two DVCs
(Nxxx,Nxxx) that will communicate over FFT-NFN link.
• format Nxxx, Nxxx: Numbers of the two DVCs that will communicate over the FFT-NFN link.
• format NxxxAyyT: Use this address (N = the DVC node number and A = the DAL device address on the digital audio loop) when
no telephone control modules are installed on a DAL device's FFT riser.
Refer to the FFT-NFN section of the DVC Manual, the DS-DB Digital Amplifier Manual, and the DAA2 and DAX Amplifiers Manual for
programming and application examples.
ACS LED Designations
The LEDs on an ACM-16AT or ACM-24AT each have a user defined meaning, depending on how the NCA-2 is programmed. For each
point programmed in NCA-2, the annunciator has two lights. The colors of these lights may vary depending on the model of the annun-
ciator. On the ACM-24AT, the colors of the lights may be dynamically reprogrammed. We will use the designation 'state' for the top
light, and 'status' for the bottom light.
NOTE: For Canadian Applications (Regional Setting set to Canada):
ACS points programmed as Acknowledge, Signal Silence, System Reset and Drill will not function.
Program each point in one of the following ways:
1.
ACKNOWLEDGE
• The state light is on if there are any fire alarms in the system.
• The status light is on if there are any troubles in the system.
• Other types of events are not annunciated at the ACS board level.
• Pressing the button is analogous to pressing the 'ACKNOWLEDGE' soft key of the NCA-2, i.e. either one fire alarm will be
acknowledged, or troubles and so forth will be block acknowledged. The lights will continue to blink until all corresponding
events are acknowledged.
2.
SIGNAL SILENCE - There are two cases: the node number may be 0 (all mapped nodes) or the node number may be a specific
node.
a.All Mapped Nodes - This reflects the silence status as shown on the NCA-2 silence light.
• Neither light is ever on.
• Pressing the button attempts to silence all mapped nodes.
b.Specific Node - This reflects the silence status of a single node.
• Neither light is ever on.
• Pressing the button attempts to silence the single node.
3.
SYSTEM RESET - There are two cases: the node number may be 0 (all mapped nodes) or the node number may be a specific
node.
a.All Mapped Nodes
• Neither light is ever on.
• Pressing the button attempts to reset all mapped nodes.
b.Specific Node
• Neither light is ever on.
• Pressing the button attempts to reset the single node.
4.
DRILL - There are two cases: the node number may be 0 (all mapped nodes) or the node number may be a specific node.
a.All Mapped Nodes
• The state light is on if any mapped node has entered the drill state.
• The status light is never on.
• Pressing the button attempts to drill all mapped nodes.
b.Specific Node
• The state light is on if the node has entered the drill state.
NCA-2 Manual — P/N 52482:M5 03/20/2019
Programming
77