Panel Program Menu
ACS Point
Mode
Disable
This point will enable/disable a specified point, zone or logic zone on an NFS2-
3030, as well as DAA speaker circuit(s).
CAUTION: When a disabled output is enabled, it will be affected by conditions
existing in the system that would normally affect it. For example, when a condition
exists in the system that would normally turn the output ON, the output will turn ON
when it is enabled.
Acknowledge This point will act like an Acknowledge soft key or button on the panel,
acknowledging a single fire alarm event or block acknowledging other events when
its button is pushed.
Note: For Canadian Applications, if the DCC option is disabled (subject to AHJ
approval), Acknowledge will function as stated.
Silence
This point will silence the silenceable outputs on one panel or all panels that are
mapped to the NCA-2, depending on programming.
Note: For Canadian Applications, if the DCC option is disabled (subject to AHJ
approval), Signal Silence will function as stated.
System Reset This point will reset one panel or all panels that are mapped to the NCA-2,
depending on programming.
Note: For Canadian Applications, if the DCC option is disabled (subject to AHJ
approval), System Reset will function as stated.
Drill
This point will initiate a fire drill when its button is pushed for one panel or all panels
that are mapped to the NCA-2, depending on programming.
Note: Not for use in Canadian Applications.
Enable
This point will cause the associated input (a DVC's Telephone, RM-1, AUX A or
Paging
AUX B) to become an active audio source on Noti•Fire•Net. The user may then
choose to activate specific PAM points on remote Digital Voice Commands to use
this network input, or to perform a paging function such as ALL CALL from this
input.
All Call
This point will activate ALL CALL. (Speaker Circuits will be turned on according to
programming.)
Mapping can include either all nodes (program the node = 0) or a single node
(program the node = the node number.)
NOTE: Re: AMG-1 - If the ALL CALL function is programmed for a Node 0 ACS
point in a specific NCA-2, pressing the ALL CALL button will activate the AMG-1s
and Speaker circuits on nodes that are mapped into that NCA-2, or as modified by
any Page functions programmed into the AMG-1 mapping at address 32.
PAGE
This point will, when pressed after an "Enable Paging From__" button, allow PAGE
INACTIVE
INACTIVE paging (Page Inactive Areas) from the source (Telephone, RM-1, AUX A
or AUX B). The Special Paging Function map programming at the DVC will receive
the page function.
FFT-NFN
....will, when pressed:
• Notify a DVC in the map formal Nxxx,Nxxx,NxxxLyyMzzz or
Nxxx,Nxxx,NxxxAyyT to open the FFT-NFN link and turn on the mapped FFT
point or riser. A second press will notify the DVC to turn off that FFT point or riser
and determine whether the FFT-NFN link should be closed or remain open.
• Notify the DVC in the map format Nxxx,Nxxx to close or open the FFT-NFN link
between two DVCs.
Page Evac
...will, when pressed after an "Enable Paging" button, allow PAGE EVAC paging
from that source (Telephone, RM-1, AUX A or AUX B). The Special Paging
Function map programming at the DVC will receive the page function.
Page Alert
...will, when pressed after an "Enable Paging" button, allow PAGE ALERT paging
from that source (Telephone, RM-1, AUX A or AUX B). The Special Paging
Function map programming at the DVC will receive the page function.
NCA-2 Manual — P/N 52482:M5 03/20/2019
Function:
Table 5.4 ACS Point Mapping: Explanation of Point Modes (2 of 3)
Programming
Explanation
The Point Active LED is lit if the
corresponding mapped point or zone
is active. The Status (trouble) LED is
lit if that point or zone is disabled.
The Point Active LED is lit when there
are any fire alarms in the system. The
Status (trouble) LED is lit when there
are troubles in the system.
The Point Active LED is lit if all
silenceable outputs have been
silenced. The Status (trouble) LED is
lit if not all silenceable outputs have
been silenced after the button is
pushed.
No LED will ever light at this point.
The Point Active LED is lit if a
corresponding mapped point is active.
The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a
corresponding mapped point is active.
The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a
corresponding mapped point is active.
The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a
corresponding mapped point is active.
The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a
corresponding mapped point is active.
The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a
corresponding mapped point is active.
The Status (trouble) LED is on when a
point or zone is in trouble.
The Point Active LED is lit if a
corresponding mapped point is active.
The Status (trouble) LED is on when a
point or zone is in trouble.