Siemens LMV51 Series Basic Documentation page 294

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Modulating burners
Multistage burners
294/301
Siemens Building Technologies
HVAC Products
21.3.3
With software version V01.50 or higher, Pt100 sensors
in operating mode 6 are permitted
New load controller function for manipulated variable input and
load output
Manipulated variable input, modulating:
< 3 mA open-circuit
4 mA
or 2 V
20 mA
or 10 V
Burner shutdown at < 5 mA not used.
Load output, modulating:
< 3 mA Open-circuit
4 mA
0 % load
xx mA
Low-fire (min. load)
xx mA
High-fire (max. load)
20 mA
100 % load
Shutting the burner down = no impact on signal.
Manipulated variable input, multistage burner:
Stage 1:
5 mA
or 2.5 V
Stage 2:
10 mA or 5 V
Stage 3:
15 mA or 7.5 V
Switching thresholds at:
7.5 mA and 12 mA
with 0.5 ma hysteresis
3.75 V
and 6.25 V
with 0.25 V hysteresis
Burner shutdown at < 5 mA not used.
< 3 mA: Open-circuit
Load output, multistage:
Burner off:
4 mA
Stage 1:
5 mA
Stage 2:
10 mA
Stage 3:
15 mA
The load controller's software has been changed from V01.50 to V01.60.
The following changes have been introduced:
21.3.4
Plausibility check at inputs X61 and X62
The plausibility check at inputs X61 and X62 is not made anymore. This means that fast
value changes at these inputs will no longer result in safety shutdown.
Basic Documentation LMV5...
21 Revision history
low-fire (min. load)
high-fire (max. load)
CC1P7550en
13.08.2004