Siemens LMV51 Series Basic Documentation page 209

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
15
01
SA
15
02
SA
15
04
SA
15
08
SA
15
10
VSD module Fan Speed not reached
15
20
SA
16
#
BU
16
00
BU
16
01
BU
16
02
BU
16
03
BU
16
04
BU
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Fault Positioning Actuator
Positioning fault air actuator
Fault Positioning Actuator
Positioning fault fuel actuator
Fault Positioning Actuator
Positioning fault auxiliary actuator 1
Fault Positioning Actuator
Positioning fault auxiliary actuator 2
The fan in combination with the VSD has
not reached the required speed
Fault Positioning Actuator
Positioning fault auxiliary actuator 3
Internal Fault Basic Unit
Basic unit has detected a plausibility fault
in the ratio control system.
The diagnostic code describes the cause
of the fault.
Internal Fault Basic Unit
Ratio curve of the air actuator is not fully
defined
Internal Fault Basic Unit
Ratio curve of the fuel actuator is not fully
defined
Internal Fault Basic Unit
Ratio curve of auxiliary actuator 1 is not
fully defined
Internal Fault Basic Unit
Ratio curve of auxiliary actuator 2 is not
fully defined
Internal Fault Basic Unit
Ratio curve of auxiliary actuator 3 is not
fullydefined
Meaning for the LMV5x system
Troubleshooting
Check characteristics of VSD for linearity. Remove filters,
damping and delay members
Check the curve to see if correct values have been entered
for the air actuator. Readjust the ratio curve, if required
Check the curve to see if correct values have been entered
for the fuel actuator. Readjust the ratio curve, if required
Check the curve to see if correct values have been entered
for auxiliary actuator 1. Readjust the ratio curve, if required
Check the curve to see if correct values have been entered
for auxiliary actuator 2. Readjust the ratio curve, if required
Check the curve to see if correct values have been entered
for auxiliary actuator 3. Readjust the ratio curve, if required
209/301
CC1P7550en
13.08.2004