Siemens LMV51 Series Basic Documentation page 244

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
AB
13
O2M
AB
15
O2M
AB
16
O2M
AB
17
O2M
AB
18
O2M
AB
19
O2M
AB
1A
O2M
AB
1B
O2M
AB
20
O2M
AB
21
O2M
AB
22
O2M
AB
23
O2M
AB
24
O2M
AB
25
O2M
AB
30
O2M
244/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Unplaus Value Compensation
Compensation element voltage outside
Element
the valid range
Unplaus Value Flue Gas Temp
Temperature of combustion air sensor
O2 Module
outside the valid range (-20...+400 °C)
Unplaus Value Flue Gas Temp
Temperature of flue gas sensor outside
O2 Module
the valid range (-20...+400 °C)
Internal Fault O2 Module
Fault during combustion air temperature
sensor test
Internal Fault O2 Module
Fault during thermocouple test
Internal Fault O2 Module
Fault during compensation element test
Internal Fault O2 Module
Fault during channel comparison of O2
signal
Internal Fault O2 Module
Fault ADC test voltages
O2 Sensor Temp too low
Temperature of QGO measuring cell too
low
O2 Sensor Temp too high
Temperature of QGO measuring cell too
high
Internal Fault O2 Module
Fault during calculation test
Unplaus Value Ri 02 Measuring
Measured internal resistance of the QGO
Cell
measuring cell is smaller than 5 Ohm or
greater than 150 Ohm
Response Time O2 Measuring
Measured response time of the QGO
Cell too long
measuring cell exceeds 5 s
O2 Sensor Test aborted by O2
Fault occurred during O2 sensor test
Module
Internal Fault O2 Module
CAN fault
Meaning for the LMV5x system
Troubleshooting
Check connections (polarity, short-circuit, open-circuit).
Check housing temperature of the QGO (temperature inside
-25...120 °C)
Check connections (short-circuit, open-circuit).
Check ambient temperature
Check connections (short-circuit, open-circuit).
Check ambient temperature
*2)
*2)
*2)
*2)
*2)
Check mains power supply on O2 module.
Check fuse F2 on O2 module.
Check connection between O2 module and QGO heating
Check QGO temperature
*2)
Check electrical connection (polarity, short-circuit).
If fault occurs after more than 1 year, QGO may have
reached the end of its service life -> replace
Check mounting position of QGO.
Check to see if QGO is dirty.
If error occurs after more than 1 year, QGO may have
reached end of its service life -> replace
Check fluctuations of the O2 value
*2)
CC1P7550en
13.08.2004