Siemens LMV51 Series Basic Documentation page 213

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
1C
01..3F
BU
1C
01
BU
1C
02
BU
1C
04
BU
1C
08
BU
1C
10
BU
1C
20
BU
1D
#
BU
1D
01..3F
BU
1D
01
BU
1D
04
BU
1D
08
BU
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Ignition Pos not defined
The diagnostic value is made up of the fol-
lowing faults or their combinations (the in-
dividual diagnostic codes are added up in
hexadecimal format)
Ignition Pos not defined
Ignition position of the air actuator
Ignition Pos not defined
Ignition position of the active fuel actuator
has not been parameterized
Ignition Pos not defined
Ignition position of auxiliary actuator 1 has
not been parameterized
Ignition Pos not defined
Ignition position of auxiliary actuator 2 has
not been parameterized
Ignition Pos not defined
Ignition position of VSD has not been pa-
rameterized
Ignition Pos not defined
Ignition position of auxiliary actuator 3 has
not been parameterized
Running time fault of actuators / VSD.
Fault Running Time
The diagnostic value is made up of the fol-
lowing faults or their combinations (the in-
dividual diagnostic codes are added up in
hexadecimal format)
Fault Running Time Air Actuator
Running time fault of air actuator
Fault Running Time Aux Actuator Running time fault of auxiliary actuator 1
Fault Running Time Aux Actuator Running time fault of auxiliary actuator 2
Meaning for the LMV5x system
Troubleshooting
Check the relevant actuators to see if they are mechanically
overloaded. Check power supply to the actuators and their
fuses.
The actuator's ramp must be smaller to or equal to the
ramp parameterized in the basic unit.
The parameterized ramp of the VSD must be smaller than
the ramp parameterized in the basic unit (recommendation:
20 %)
213/301