Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1
Menu level 2
Menu level 3
128/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
7 Display and operating unit AZL5...
Menu level 4
Menu level 5
Menu level 6
SensExtranlGas
SensPilotPhGas
SensOperPhGas
SensExtranlOil
SensPilotPhOil
Description
QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOT QRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOT QRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
QRI (QRB) AND ionization
QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOT QRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
QRI (QRB) AND ionization
QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOT QRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOT QRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
Value range
Access
Default pa-
LMV51 LMV52
rights
rameter
setting
1 Sensor
OEM
1 sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
1 Sensor
OEM
1 sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
QRI_B & ION
1 Sensor
OEM
1 sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
QRI_B & ION
1 Sensor
OEM
1 sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
1 Sensor
OEM
1 sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
CC1P7550en
x
x
x
x
x
13.08.2004

Hide quick links: