Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Internal Fault Basic Unit
Safety time 1 oil too long
Internal Fault Basic Unit
Ignition off time > TSA1 gas
Internal Fault Basic Unit
Ignition off time > TSA1 oil
Internal Fault Basic Unit
Safety time 2 gas too long
Internal Fault Basic Unit
Safety time 2 gas too long
Fault at deactivated inputs
Controller connected but deacti-
Controller input connected but deacti-
vated
vated
Air Press Switch connected but
APS connected but deactivated
deactivated
FCC / FGR – APS connected but
FCC / FGR – APS connected but deacti-
deactivated
vated
Gas Pressure min connected but
GP-Min connected but deactivated
deactivated
Gas Pressure max connected but
GP-Max connected but deactivated
deactivated
Oil Pressure min connected but
OP-Min connected but deactivated
deactivated
Oil Pressure max connected but
OP-Max connected but deactivated
deactivated
Start Signal Oil connected but de-
Start signal oil connected but deactivated
activated
HO Start connected but deacti-
HO start connected but deactivated
vated
Start Signal Gas connected but
Start signal gas connected but deacti-
deactivated
vated
Locked by SLT
Shutdown via SLT test
Programstop active
Program stop was activated. System has
stopped at the parameterized position
Programstop active
Program stop "STOP_DR_PREP" in
Phase 24 active
Meaning for the LMV5x system
Troubleshooting
Deactivate input or do not connect
SLT was activated and safety shutdown was triggered (usu-
ally via the SLT)
Deactivate the program stop if no longer required
219/301
CC1P7550en
13.08.2004