Siemens LMV51 Series Basic Documentation page 215

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
1F
03
VSD module Speed Acquisition faulty
1F
04
VSD module Standardization canceled because
1F
05
VSD module Standardization canceled because
1F
06
VSD module Speed Test was not successfully
21
---
BU
22
---
BU
23
---
BU
23
00
BU
23
01/02/03
BU
24
---
BU
24
00
BU
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Pulse sequence and length at the speed
input were different from those antici-
pated
Fan was not able to keep the standard-
of VSD
ized speed at a constant level
Air actuator has not reached the pre-
of Air Actuator
purge position. For this reason, speed
standardization is not possible
Internal VSD module speed test was not
completed
successful
Safety Loop open
Safety chain open
Internal Temp Limiter has re-
Internal TL has switched off because pa-
sponded
rameterized value has been exceeded
Extraneous Light on Startup
Basic unit has detected extraneous light
during startup
Extraneous Light on Startup
Basic unit has detected extraneous light
during startup
Extraneous Light on Startup
(Only LMV52...) Basic unit has detected
extraneous light during startup
Coding by bits:
Bit 0 = flame QRI.../QRB... present
Bit 1 = flame ION present
Extraneous Light on Shutdown
Basic unit has detected extraneous light
during shutdown
Extraneous Light on Shutdown
Basic unit has detected extraneous light
during shutdown
Meaning for the LMV5x system
Troubleshooting
Check to see if sensor disk and speed sensor are correctly
mounted.
Check if the distance of the inductive sensor is correct.
Check if the inductive sensor is correctly connected
Check if motor runs.
Check if the inductive sensor is correctly connected.
Check if distance of inductive sensor is correct
Check to see if all air-influencing actuators travel to the pre-
purge position.
Check to see if the relevant actuators are mechanically over-
loaded or replace defective actuator, if necessary.
Check power supply to the actuators
215/301
CC1P7550en
13.08.2004