16 Addendum 1: List of fault status messages of LMV5... system
Display
Internal Fault O2 Module
CRC fault of a parameter page
Internal Fault O2 Module
Page too long open
Internal Fault O2 Module
Page disrupted
Internal Fault O2 Module
Invalid access to parameters
Meaning for the LMV5x system
Troubleshooting
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL5... pa-
rameters.
Otherwise, replace defective O2 module
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL5... pa-
rameters.
Otherwise, replace defective O2 module
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL5... pa-
rameters.
Otherwise, replace defective O2 module
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL5... pa-
rameters.
Otherwise, replace defective O2 module