Siemens LMV51 Series Basic Documentation page 229

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
99
---
All
9A
---
All
9B
#
All
9B
01
All
9B
02
All
A0
#
SA
A0
See A1
See A1
A1
#
SA
A1
01
SA
A1
02
SA
A1
04
SA
A1
05
SA
A1
07
SA
A1
08
SA
A1
09
SA
A1
0C
SA
A1
0D
SA
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Internal Fault Basic Unit
CAN is in bus off
Internal Fault Basic Unit
CAN warning level.
Fault probably occurred when connecting
or disconnecting a CAN bus user
Internal Fault Basic Unit
CAN queue overrun
Internal Fault Basic Unit
Overrun of RX queue
Internal Fault Basic Unit
Overrun of TX queue
Auxiliary actuator 3 has detected a fault
and reported it to the basic unit.
Type of fault: See diagnostic code
See A1
Air actuator has detected own fault and
reported it to the basic unit.
Type of fault: See diagnostic code
Internal Fault Air Actuator
CRC fault during ROM test
Internal Fault Air Actuator
CRC fault during RAM test
Internal Fault Air Actuator
Fault during key value check
Internal Fault Air Actuator
Error code for time block overflow
Internal Fault Air Actuator
Sync fault or CRC fault
Internal Fault Air Actuator
Error code for main loop counter
Internal Fault Air Actuator
Fault during stack test
Overtemperature Air Actuator
Temperature warning and shutdown
Internal Fault Air Actuator
Actuator turns in the wrong direction
Meaning for the LMV5x system
See A1
Troubleshooting
Check CAN cabling
*1)
Check CAN cabling
*1)
Check CAN cabling
*1)
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
See A1
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
Check housing temperature (max. 60 °C)
229/301
CC1P7550en
13.08.2004