16 Addendum 1: List of fault status messages of LMV5... system
Display
Internal Fault Basic Unit
VSD curve is not fully defined
Internal Fault Basic Unit
Calculated P-part outside the permissible
range
Internal Fault Basic Unit
Calculated I-part outside the permissible
range
Internal Fault Basic Unit
Calculated system delay time outside the
permissible range
Internal Fault Basic Unit
Calculated O2 setpoint outside the permis-
sible range
Internal Fault Basic Unit
Calculated O2 min. value outside the per-
missible range
Internal Fault Basic Unit
Calculated O2 ratio value outside the per-
missible range
Internal Fault Basic Unit
The load / point number predefined by the
AZL... lies outside the permissible range
Internal Fault Basic Unit
Calculated standardized value lies outside
the permissible range
Internal Fault Basic Unit
With hysteresis compensation: Permissible
target positioning range exceeded
Internal Fault Basic Unit
The load / point number predefined by the
AZL... lies outside the permissible range
Meaning for the LMV5x system
Troubleshooting
Check the curve to see if correct values have been entered
for the VSD. Readjust the ratio curve, if required
Check to see if correct values have been entered for the
controller parameters. Readjust O2 trim control, if required,
or repeat the settings
Check to see if correct values have been entered for the
controller parameters. Readjust O2 trim control, if required,
or repeat the settings
Check to see if correct values have been entered for the
controller parameters. Readjust O2 trim control, if required,
or repeat the settings
Check to see if correct values have been entered for the O2
setpoints. Readjust O2 trim control, if required, or repeat
the settings
Check to see if correct values have been entered for the O2
min. values. Readjust O2 trim control, if required, or repeat
the settings
Check to see if the correct values have been entered for the
O2 ratio values. Readjust O2 trim control, if required, or re-
peat the settings
*1)
Check if the correct values have been entered for the stan-
dardized values. Readjust O2 trim control, if required, or re-
peat the settings
*1)
*1)
CC1P7550en