Siemens LMV51 Series Basic Documentation page 221

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
58
---
BU
59
#
BU
59
#
BU
5A
#
BU
5A
#
BU
5B
#
BU
5B
#
BU
5C
#
BU
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Parameter Set damaged
Internal communication (µC1 <> µC2)
Parameter Set damaged
After initialization, EEPROM page is on
ABORT (last parameterization was pos-
sibly interrupted due to a power failure)
Parameter Set damaged
Page number
Parameter Set damaged
CRC error of a parameter page
Parameter Set damaged
Page number
Parameter Set damaged
Page is on ABORT
Parameter Set damaged
Page number
Parameter Backup Restore
Page is on WR_RESTO
A backup restore was made
Meaning for the LMV5x system
Troubleshooting
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL... pa-
rameters.
Otherwise, replace defective basic unit
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL... pa-
rameters.
Otherwise, replace defective basic unit.
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL... pa-
rameters.
Otherwise, replace defective basic unit
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL... pa-
rameters.
Otherwise, replace defective basic unit
Reset the unit.
221/301
CC1P7550en
13.08.2004