Siemens LMV51 Series Basic Documentation page 241

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
A9
#
VSD module Fault VSD Module
A9
01
VSD module Internal Fault VSD Module
A9
02
VSD module Internal Fault VSD Module
A9
04
VSD module Internal Fault VSD Module
A9
05
VSD module Internal Fault VSD Module
A9
07
VSD module Internal Fault VSD Module
A9
08
VSD module Internal Fault VSD Module
A9
09
VSD module Internal Fault VSD Module
A9
0A
VSD module Internal Fault VSD Module
A9
0C
VSD module Alarm from VSD
A9
0D
VSD module Control Range Limitation VSD
A9
0E
VSD module Internal Fault VSD Module
A9
15
VSD module Internal Fault VSD Module
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
VSD module has detected own fault and
reported it to the basic unit.
Type of fault: See diagnostic code
CRC fault during ROM test
CRC fault during RAM test
Fault during key value check
Error code for time block overflow
Sync fault or CRC fault
Error code for main loop counter
Fault during stack test
Max IRQ speed reached
VSD reports a fault to the VSD module
VSD module could not offset speed differ-
Module
ential within its control limits
Fault during the speed calculation test
CAN bus fault, disturbed CAN bus trans-
missions
Meaning for the LMV5x system
Troubleshooting
*1)
*1)
*1)
*1)
*1)
*1)
*1)
Possibly interference on the line to the speed sensor, check
cable routing, use shielding
*1)
Fault has been triggered by the VSD.
Read VSDs error code.
Check VSD settings (ramps, motor settings), increase ramp
time on VSD and basic unit, if necessary.
Check combination VSD / motor size
Check to see if the current interfaces of VSD and VSD
module use the same setting (0/4...20 mA).
Standardize the speed.
!! Note !!
After standardizing the speed -> check setting of combus-
tion mixture !
*1)
If fault occurs sporadically: Check CAN bus wiring.
Improve EMC.
Check terminating resistors and correct, if necessary
241/301
CC1P7550en
13.08.2004