Siemens LMV51 Series Basic Documentation page 207

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
05
#
BU
05
01
BU
05
02
BU
05
03
BU
06
#
BU
06
01
BU
06
02
BU
06
03
BU
06
04
BU
10
#
BU
10
01
BU
10
02
BU
10
03
BU
10
04
BU
10
05
BU
10
06
BU
10
07
BU
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Fault Flame Detector Test
Fault during test of the flame signal am-
plifier
Fault Flame Detector Test
Fault during test of the flame signal am-
plifier
Fault Flame Detector Test
Crosstalk fault between test pin and
flame signal amplifier channel (with
LMV52... FSVchannel QRI... / QRB...)
Fault Flame Detector Test
(Only LMV52...) crosstalk fault between
test pin and FSV channel ION
Internal Fault Basic Unit
Fault internal hardware tests
Internal Fault Basic Unit
Fault during test of the ignition relay
Internal Fault Basic Unit
Fault during test of the safety relay
Internal Fault Basic Unit
Fault during voltage supervision test
Internal Fault Basic Unit
Relay voltage not switched off after reset
Internal Fault Basic Unit
Basic unit has detected an inadmissible
circuit at one of the outputs, a faulty di-
ode, or a short-circuit in the power supply
of the contact feedback network. The di-
agnostic codes indicates the input af-
fected
Internal Fault Basic Unit
Load controller on / off
Internal Fault Basic Unit
Fan contact
Internal Fault Basic Unit
Selection of oil-firing
Internal Fault Basic Unit
Selection of gas-firing
Internal Fault Basic Unit
Reset
Internal Fault Basic Unit
Pressure switch oil maximum
Internal Fault Basic Unit
Pressure switch oil minimum
Meaning for the LMV5x system
Troubleshooting
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace flame detector or replace
defective basic unit
*1)
Check wiring of outputs, check connection of the neutral con-
ductor to the devices used.
The fault may be caused by capacitive loads which, with the
relay deenergized, are the reason the voltage takes more
than about 10 ms to drop to zero.
Check wiring to the load
*1)
207/301
CC1P7550en
13.08.2004