Siemens LMV51 Series Basic Documentation page 224

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
71
---
BU
72
#
BU
72
01
BU
72
02
BU
72
03
BU
72
04
BU
80
#
SA
80
01
SA
80
02
SA
80
03
SA
81
#
SA
81
01
SA
81
02
SA
81
03
SA
224/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Manual Lockout
Lockout was made manually via contact Lockout via the external reset / lockout contact is negated
Internal Fault Basic Unit
Plausibility fault in connection with fault
entry
Internal Fault Basic Unit
Fault in "seterr()"
Internal Fault Basic Unit
Fault in "seterr()"
Internal Fault Basic Unit
Fault in "error_manager()"
Internal Fault Basic Unit
Fault in "storeerr()"
Fault Feedback Aux Actuator 3
Basic unit has detected wrong state of
the air actuator
Fault Feedback Aux Actuator 3
CRC error
Fault Feedback Aux Actuator 3
Key error main loop counter
Fault Feedback Aux Actuator 3
No feedback for max. number
Fault Feedback Air Actuator
Basic unit has detected wrong state of
the air actuator
Fault Feedback Air Actuator
CRC error
Fault Feedback Air Actuator
Key error main loop counter
Fault Feedback Air Actuator
No feedback for max. number
Meaning for the LMV5x system
Troubleshooting
by new actuation
*1)
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
CC1P7550en
13.08.2004