Siemens LMV51 Series Basic Documentation page 187

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Description of the connection terminals (cont'd)
Connection symbol
X5-01
PIN1
PIN2
PIN3
X5-02
PIN1
PIN2
PIN3
X5-03
PIN1
PIN2
PIN3
PIN4
X6-01
PIN1
PIN2
PIN3
PIN4
X6-02
PIN1
PIN2
PIN3
X6-03
PIN1
PIN2
PIN3
X7-01
PIN1
PIN2
PIN3
X7-02
PIN1
PIN2
PIN3
X7-03
PIN1
PIN2
PIN3
Siemens Building Technologies
HVAC Products
Description
x
Protective earth (PE)
x
Pressure switch min-oil (DWmin-oil)
x
Power signal for pressure switch-min-oil
(DWmin-oil)
x
Protective earth (PE)
x
Pressure switch-max-oil (DWmax-oil)
x
Power signal for pressure switch-max-
oil (DWmax-oil)
x
Controller (ON / OFF)
x
Controller closes / stage 3
x
Controller opens / stage 3
x
Power signal for control of controller
x
Start release oil
x
Power signal start release oil
x
Direct heavy oil start
x
Power signal direct heavy oil start
x
Protective earth (PE)
x
Neutral conductor (N)
x
Oil pump / magnetic coupling
x
Protective earth (PE)
x
Neutral conductor (N)
Fuel valve SV (oil)
x
Protective earth (PE)
x
Neutral conductor (N)
Fuel valve V2 (oil)
x
Protective earth (PE)
x
Neutral conductor (N)
Fuel valve V3 (oil)
x
Protective earth (PE)
x
Start release gas CPL (LMV52...)
x
Power signal (reserve)
Basic Documentation LMV5...
11 Description of the connection terminals (AC 230 V)
Electrical rating
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
2 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
1 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
1 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
1 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
CC1P7550en
13.08.2004