Power Supply Wiring; Connecting The Slice I/O Terminal Power Supply - Omron SmartSlice GRT1 Series Operation Manual

Slice i/o units
Hide thumbs Also See for SmartSlice GRT1 Series:
Table of Contents

Advertisement

Power Supply Wiring

Installing the End
Plates
Note
3-2

Power Supply Wiring

3-2-1

Connecting the Slice I/O Terminal Power Supply

Evaluating the Power
Supply Requirements
Unit Power Supply
1,2,3...
Always secure the Slice I/O Terminal on the DIN Track by installing End Plates
on both sides of the Terminal. First hook the bottom of the End Plate on the
bottom edge of the DIN Track (1), attach the top of the End Plate, and pull the
End Plate down onto the top edge of the DIN Track (2).
Tighten the End Plate's securing screw.
End Plate
Always secure the Slice I/O Terminal by attaching End Plates on both ends.
Both the Slice I/O Terminal power supply and the external I/O power supply
are connected with screwless clamping-type terminals on the Communica-
tions Unit.
The Communications Unit has two sets of power supply terminals for the fol-
lowing two systems.
Power supply
terminals
Unit power supply
These terminals supply power to the Communications Unit's
terminals
internal circuits as well as the connected Slice I/O Units' inter-
nal circuits (supplied through the Slice bus).
I/O power supply ter-
These terminals supply power to the external I/O that is con-
minals
nected to the Terminal's Slice I/O Units.
The maximum power consumption for a Slice I/O Terminal is 80 W per block.
1. Calculate the power consumption of all of the Slice I/O Units connected to
the Communications Unit.
2. If the power consumption exceeds 80 W, mount a Right Turnback Unit
(GRT1-TBR) on the Slice I/O Unit at the point where the power consump-
tion is less than 80 W.
3. Connect the 24 VDC Unit power supply to the Left Turnback Unit (GRT1-
TBL).
Section 3-2
2
1
End Plate
End Unit
Description
31